| Materials: - Valve body: | DZR BRASS |
| Â | - Regulating spindle: | | Â | - Internal shutter: | | Â | - Sealing elements: | | Â | - Cover: |
| | Â | DZR BRASS | | Â | PPO | | Â | EPDM | | Â | ABS |
|
| Â |
| Temperature adjustment range: | 85÷120°F (29÷49°C) |
| Temperature set: | must be commissioned on site to achieve desired temperature |
| Temperature control: | ±3°F (±2°C) |
| Â |
| Minimum cold inlet temperature: | 39°F (4°C) |
| Minimum cold inlet temperature: | 85°F (29°C) |
| Minimum hot inlet temperature: | 120°F (49°C) |
| Minimum hot inlet temperature: | 185°F (85°C) |
| Wire Length: | 10.50" |
| Â |
| Maximum working pressure (static): | 140 psi (10 bar) |
| Maximum working pressure (dynamic): | 70 psi (5 bar) |
| Maximum working pressure (dynamic): | 1.5 psi (0.1 bar) |
| Â |
| Maximum unbalanced dynamic supply (hot/cold or cold/hot): | 6:1 |
| Â |
| Minimum temperature differential between hot water inlet and mixed water outlet to ensure thermal shutoff function: | 18°F (10°C) |
| Minimum temperature differential between mixed water outlet and cold water inlet to ensure stable operation: | 9°F (5°C) |
| Minimum flow rate for stable operation: | 1 gpm (4 l/min) |
| Certified to: | ASSE 1016 |